YASKAWA robots with YRC1000 alarm 1512 or 1513 need a controller cooling check before a power unit is condemned. In the manufacturer alarm manual, 1512 is POWER SUPPLY FAN ERROR(SERVO). Alarm 1513 is POWER SUPPLY OVERHEAT(SERVO). They point to related but different evidence: fan speed and a power-unit temperature alarm.

This YASKAWA robot repair guide follows airflow, fan operation, connections and the CPS01K* unit. The asterisk is the manual’s family notation, not a complete order code. Confirm the installed controller and unit labels before using any connector or replacement reference. A robot model name alone does not identify its cabinet configuration.

YASKAWA robots: controller identity and repair guides

1. Separate alarm 1512 from YRC1000 alarm 1513

The manual describes YRC1000 alarm 1512 as decreased rotation speed of an in-panel cooling fan. For YRC1000 alarm 1513, it states that the temperature sensor in the CPS01K* unit has activated and the controller’s internal temperature has risen abnormally. The alarm descriptions do not provide one universal fan-speed or cabinet-temperature acceptance number.

What to preserve before resetting
RecordWhy it mattersNext question
First alarm and later messagesA fan alarm may precede heat-related stopsWhich event occurred first?
Time from start and operating stateA delayed stop differs from an immediate alarmWas the cabinet cold or already warm?
Ambient and cabinet conditionsA blocked path can affect a working fanWhat changed around the inlet and outlet?
Controller and power-unit labelsWiring and replacement options depend on configurationDoes the manual match this installed unit?

2. Inspect the complete airflow path

Record external cabinet conditions before moving equipment. Check whether stored material, a wall or added covers obstruct the inlet or outlet. Look for dust mats and changes to the room cooling. A fan can turn while the intended air path remains blocked. Compare the installed arrangement with the cabinet maintenance instructions.

For internal inspection, isolate the cabinet and follow its discharge procedure. Inspect permitted filters, grilles and cooling passages using the specified maintenance method. Keep debris out of the electronics. Do not remove barriers or run production with the cabinet open as a substitute for restoring its designed cooling path.

3. Distinguish a fan defect from a connection problem

Inspect the fan assembly for damaged blades, rubbing, obstruction and the correct orientation. Check its label, mounting and wiring against the installed parts information. A replacement must match the required electrical rating, airflow arrangement, connector and monitoring function. Similar dimensions alone do not establish that a generic fan will work.

The manual lists a control power supply unit fan, CSRA-CPS01K*-FN, as a remedy option for 1512 in the configuration described. Confirm the full applicable part with the exact unit documentation. Powered checks of fan supply or monitoring signals need the correct test points and qualified personnel. Do not bridge the fan monitoring circuit to clear an alarm.

4. Check the named connectors only on the matching system

For both 1512 and 1513, the manual’s connection branch names CPS01K* CN158 and ACP01 CN101. In a coordinated system, it also names the slave controller path at CPS01K* CN158 and SDCA01 CN509. Verify board identity and the wiring drawing before following those references; they are not a universal map for every Yaskawa controller.

With the system isolated, inspect seating, locks, recessed contacts, heat marks and cable strain. Record the connector and defect rather than reporting only that the wires were checked. Any continuity or powered measurement must follow the circuit documentation. Reseating a plug without finding the cause is not evidence that an intermittent fault is solved.

5. Decide whether the fan or power supply needs repair

Use findings to define the component work
FindingWork to evaluateEvidence after work
Blocked inlet or cooling pathRestore the specified airflow arrangementCondition of path and observed thermal trend
Fan fails its applicable checksCorrect fan assembly replacementSupply, fan operation and alarm state
Damaged connectionDocumented connector or harness repairSeating and permitted circuit checks
Persistent CPS01K* unit faultUnit assessment or matching replacementApplicable unit tests and installed-system verification

For 1513 the manufacturer includes checking the cooling fans and replacing a faulty fan. A CPS01K* unit failure is a separate branch. Do not replace the complete unit solely because the cabinet became hot. If the alarm returns after the listed checks, preserve CMOS.BIN as instructed and send the occurrence conditions to the service contact.

6. Keep amplifier overheat on its own branch

The same manual lists 1514 as OVERHEAT(AMPLIFIER). Its connection and module checks differ from the 1512/1513 entries. If 1514 appears, use its own alarm procedure and installed hardware details. Sharing a word such as overheat does not make every power, amplifier and motor alarm the same fault.

Motor overheating can also involve the load, brake or feedback rather than cabinet cooling. Follow the separate motor guide when the evidence points to that assembly. Preserve the complete alarm sequence before changing parts, then confirm which symptoms remain after each documented correction.

Servo motor overheating: separate load and motor evidence

7. Verify cooling after the repair

Before energizing, check the fan fit, connectors, guards, cooling path and any required protective-earth connection. Restore the approved cabinet arrangement. During controlled power-up, record fan behaviour and the alarm state using the allowed observation method. Confirm that the fault does not return immediately; a reset alone is not the full test.

Then run an agreed installed-system cycle with the cabinet closed as designed. Record ambient conditions, tool and load, duration and any measured temperature trend. Compare with the applicable limits and the original failure conditions. A short cold start cannot establish stability during a warm production cycle. List conditions that were not reproduced.

Prepare a useful cooling-fault enquiry

Send the controller, CPS01K* and fan labels, complete first alarm and a brief event timeline. Include inlet/outlet and connector photographs taken under the site procedure. Note recent filter, fan, cabinet or room changes. Our team can review the available evidence and clarify the inspection scope, parts identity and proposed acceptance checks.

Official YRC1000 Alarm Codes: 1512, 1513 and 1514, PDF pages 362–363

YASKAWA robots not moving: enable, I/O and servo checks